CP Remote by C Mation

CP RemoteT

  • Complete Remote Monitoring & Control Solution for Corrosion Protection Systems
    • Precision control, automated testing, and remote monitoring & control in a single package
    • Synchronized control of rectifiers
    • Local & remote data recording of system variables
      • Instant off/on cycle readings, volts, amps
      • Over 100,000 data points stored locally
    • Status & alarm notification
      • User programmable
      • Structure-to-soil out of range
      • Email, fax, pager
    • Flexible communications options
      • Radio, VSAT, phone lines

Description

CP Remote

CP-Remote is a Remote Monitoring and Control System for operating Cathodic Protection Rectifiers. The System integrates precision control, automated testing, and remote monitoring into a single industrial strength package.


The CP-Remote System provides the monitoring of key rectifier parameters such as Amps, Volts, Reference Cell Voltages, instant off and on of cycle readings and more.


Electrically isolated I/O channels provide the capability to read and control virtually any analog or digital signal. The modular design can accommodate thousands of I/O channels.


A CP-Remote System provides synchronized control of rectifiers over vast geographical locations. Analog inputs directly control rectifier on/off cycles via relay outputs. The system provides for daily time schedules with user-selected times for on/off cycle scheduling.


The system clock is synchronized with a highly accurate GPS antenna to provide rectifier interruption and control of multiple units within +/- 1 millisecond accuracy.


Local and remote electronic data recording of system variables is provided. Over 16Mbytes of battery-backed RAM is available for local data storage.


Status and alarm notification can be programmed by the user to generate a message for events such as power loss, structure-to-soil potential out of range, current out of range, and more.


Battery-backed communication options allow for alarm notification of rectifier operation even with loss of site power. Email, fax, and alphanumeric pager notification are available.


Internet and network-based communications options provide simple enterprise integration including Ethernet. Wireless communications options include cell, radio, and satellite. Telephone line connections are supported.


CP-View software provides a graphical view of remote sites, alarm summary displays, real-time and historical trending of rectifier data, and flexible data recording for report generation. CP-View also supports direct connection to relational/SQL databases.


Industrial NEMA4 standard enclosures are available to meet the toughest environmental conditions. An optional 19" rack mount unit with visible status/alarm annunciation is also available.


The open system design results in a cost-effective solution while offering the user the option of customizing the system.


General Specifications

The standard configuration has been designed to operate two complete charging rectifier systems. The modular I/O system design allows for additional expansion if required.

  • Base Unit
    CPU - 16MB RAM, 8MB Flash Memory
    I/O Module Rack
    2 Analog Input Channels - mV Shunt (Amps)
    2 Analog Input Channels - 0-250VDC (Volts)
    2 Analog input Channels - 0-100VDC (Ref Cell)
    4 Digital Relay Outputs - Dry Contact or Relay
    Power Supply
    GPS Antenna/Serial Interface

  • Enclosure
    Fiberglass-reinforced polyester (FRP) enclosure;
    UL listed types 3R, 4, 4X, 12, Optional stainless
    steel unit.

(Options)


  • I/O Expansion Modules
    2 / 4 Analog Input Channels Voltage/mV/Current
    4 - Digital Output Channels DC/AC
    Wireless Communications
    Cellular Modem, Radio Modem, Telephone Modem, Satellite Communications.

    UPS - Uninterruptible Power Supply (Battery Backup)

Communication Specifications

  • Ethernet Port 10/100 Mbps Fast Ethernet (IEEE 802.3) 10Base-T & 100Base-TX, Cat 5, 1-RJ45 port
  • Serial Port 3 - EIA RS-232 Serial Ports
  • Application Protocols Modbus/TCP, Modbus RTU/ASCII, Data Highway (DH), ASCII, OPC, FTP, SNMP, SMTP, IEEE-1394 Fire wire

Physical Specifications

  • Enclosure Dimensions
    14" H x 12" W x 6" D
    3U - 19" Rack Mount Option w/ Alarm Panel

I/O Channel Specifications

  • Analog Inputs
    Voltage Inputs: +/- 150mVDC
    +/- 10VDC
    0-250VDC
    0-250V RMS VAC
    Current Inputs: +/- 20mA
    0-10 Amp RMS AC/DC
    Accuracy: 0.06% error DC
    0.2% error AC
    Optical Isolation: 4000V
    Max Volts In: Common mode up to 500V
    Impedance:1Mohm 0-250V
    100Mohm mV
  • Digital Outputs
    Solid State Relays 5-60VDC, .75amp
    12-250VAC, .75 amp
    Dry Contacts 0-130 VDC/AC
  • Additional I/O Available
    Digital Inputs: 2.5-32VDC, Dry Contact, 90-280VDC/AC
    Analog Outputs: Current 4-20ma, +/- 10VDC, 5-60VDC
    Serial Interfaces: RS-232 or RS-485

Electrical Specifications

  • Power Supply
    Input Voltage 100/120/220/230/240 VAC
    Selectable, Input Frequency 47-63 Hz
  • Battery Backup
    24hr, 4 Amp-hr

Environmental Specifications

  • Operating Temperature
    -40 to 70 ° C
  • Storage Temperature
    -40 to 85 ° C
  • Humidity
    0 - 95%, non-condensing